I thought I would go over the start-up procedure that I use. One of the issues that causes a lot of time to start up the Lykamobile from a cold start is that the boiler becomes completely filled with water from the previous cool down operation. Because the system is not vented, a vacuum is created in the boiler as everything cools down, contracts and water is drawn from the supply tanks into the boiler. This means there is no head space in the boiler the next time you want to fire up the Lykamobile to create steam.
Previously I would open up the two valves on the boiler and wait and wait and wait for the water to slowly drain out of the boiler. This works, but what a pain.
So the following procedure is what I have "boiled" everything down to. (sorry for the pun). I decided to utilize the expansion of the water during the boiler heat-up by opening the valves and allowing the expansion of the water to push the excess water out of the boiler. But first the following is done:
1. Check the steam oil reservoirs. Fill if needed. Top off the water tanks.
2. Oil everything, water pumps, valve rods, piston guide blocks etc. In my case I open up my drip oiler to give everything a dose of oil.7. Once I see mostly steam coming from both valves I close off the boiler valve and still purge water/steam through the piston/ valve chest until I see mostly steam. This also warms up the pistons and valves helping to prevent condensation etc. inside the engine. I should make a caution ! Don't drain too much, you just want to lower the amount of water in the boiler some to provide the head space for the steam. The piston/ valve box valve exhibiting steam is an indication that you now have some head space in the boiler for steam generation.
Grier,
ReplyDeleteIf you were building the car today, is there a place for
a valve to relieve the vacuum that forms on cool down?
Warm regards,
Jim Pope
Denver,CO
I believe the issue is that the water under pressure has a much higher boiling temperature. The boiler is set to 250 psi and is probably around 350 to 400 degrees in temperature. Venting the boiler to atmosphere will allow all of the liquid water to flash or steam out, thereby completely emptying out the boiler. This is not something you want to happen. The blow down valves can be used when the boiler has cooled to around 50 psi. This is done to empty out the boiler for long term storage. If you blow down the boiler at a higher pressure i.e. 250 psi, the boiler would still be too hot and warpage of the tubes etc. could possibly occur. This would cause leaks around the tubes - not good. So there is no good solution to prevent the vacuum filling of the boiler.
ReplyDeleteAfter talking with a fellow series 1 Lykamobile builder, he said that actually there is a solution. What can be done is to put in a check valve that is closed under boiler pressure and opens to atmosphere when the cool down of the boiler creates a vacuum. So in this regard, the check valve will pop open periodically to relieve the vacuum during cool down.
ReplyDelete